Does an office refurbishment mean upgrading the whole building?

Usually, no. But some required upgrades can extend beyond the fit-out itself.

Take a two-storey South Australian office built in the 1980s. The owner proposes new meeting rooms, changes to reception and refurbished toilets. The drawings show the existing stair and upper floor are to remain.

The new building work must comply with the applicable Building Rules. How far the owner needs to upgrade the existing building depends on what the proposed work triggers and the condition of the building.

In South Australia, Ministerial Building Standard MBS 001 — Upgrading health and safety in existing buildings forms part of the Building Rules. It sets minimum standards for existing buildings within its scope and recognises the need to avoid both excessive and insufficient upgrading.

Start with the scope

For this office, we’d start with the concept plan, the available approval records and what’s actually on site. Which rooms are changing? Will more people use them? Where do they enter, and how do they get out?

Those questions can change the design while a partition or doorway is still just a line on a plan.

Look beyond the line drawn around the work

The stair might be marked “existing — no work”. Even so, MBS 001 requires the alterations to maintain at least the building’s existing level of conformity with the Building Rules, including in areas outside the fit-out. If a new meeting room makes the route to the stair too long, moving its doorway may resolve the issue while retaining the stair.

Access has a separate trigger. Where the affected part requirements apply, the principal pedestrian entrance and the continuous accessible path from that entrance to the new work must comply, subject to any applicable concession. If a step at the front door prevents that access, the owner needs to allow for it in the project scope.

The same partitions also raise a useful seismic question. A fit-out that leaves the structure intact and does not increase fire safety risks falls within MBS 001’s definition of minor alterations. The 50% seismic trigger excludes that work. For an office approved before 1 January 1995 that was not designed and constructed to resist earthquake loads, more substantial alterations can trigger assessment when the areas reconfigured or structurally altered over three years exceed 50% of the building’s total floor area or volume. Altering a wall that braces the building can trigger assessment even on a much smaller job.

How TF can assist

If you’re considering a refurbishment, bring us the concept plan and any existing approvals you have. We can review what’s changing, identify which upgrades are required and explain what each requirement is responding to. That gives the owner and design team a clearer basis for deciding what can stay, where specialist input is needed and what to include in the budget.